HB012-S-06U1-S4C20
Screened Hybrid Cable, 1 x 6mm² pair power cable and 8 x singlemode optical fibers

Rev : A | Rev date : 07 Mar 2023
A hybrid cable designed to transmit both electrical power and optical signals in a single cable.
Two electrical power conductors and two fibre optic sub units, each containing four bend insensitive singlemode fibers surround a non metallic strain member.
A polyethylene UV stable jacket ensures long term operation in outdoor applications.
The fully circular construction ensures that the cable can be efficiently installed in conventional trays or ducting systems.
A corrugated aluminium screen ensures a 100% screen, enabling this cable to be installed in data and power cable ducts
 
 

FEATURES / BENEFITS

  • Circular construction prevents snagging during installation
  • Bend insensitive optical fiber simplifies installation and termination
  • Singlemode fiber provides the ultimate future proof support for high bandwidth services
  • Corrugated screen provides the ultimate cable routing flexibility
  • Water penetration (no leakage) up to 1m/24h optical core
  • Suitable for Indoor/outdoor applications

 

Hybriflex Bulk cable dia.012"Screened- DC wire dia 06mm² Unshielded, 1 DC Pair, SM x 4-pairs, CPR Jacket

 


Technical features

Structure

Cable TypeHybrid : 2 x 6mm² & 8 x SMF screened
Size1/2"
Fire PerformanceHalogen free IEC60754-1/-2 CPR: BS EN13501-6:2014 class B2ca, s1a, d1, a2

Mechanical Specifications

Outer Diameter Nominal mm (in)15.8 (0.622)
Cable Weight kg/m (lb/ft)0.235 (0.158)
Minimum Bending Radius, (Operating)mm (in)63 (2.49)
Minimum Bending Radius, (Installation)mm (in)126 (4.98)
Tensile Strength N (lb)300 (73)
Recommended / Maximum Clamp Spacing m (ft)0.6 / 1 (2 / 3.25)
Tensile Strength (Installation)1800 (397) IEC60794-1-2 E3
Crush Resistance (Operating)2000

DC Power Cable Specifications

Number of DC Pairs1
Maximum DC-Resistance Power Cable Ω/km (Ω/kft)3.3 (1.51)
Cross Section of Power Cable mm² (AWG)6 (10)
DC Wire Information84 x 0.30 PAC (Class 5)
DC Wire Jacket MaterialUV stable blue and white XLPE
DC Wire Jacket Thickness mm (in)0.5 (0.02)
DC Cable Diameter mm (in)4.4 (0.173)
DC Standards (Meets or Exceeds)IEC 60228

Cable Jacket

UV-Protection Individual and External JacketEN 50290 2 24
Jacket MaterialHalogen free IEC 60754-1/2

Armor Specifications

Armor TypeCorrugated Aluminum tube
Maximum DC-Resistance of Armor Ω/km (Ω/kft)2.42 (0.74)

F/O Cable Specifications

F/O Cable TypeTight-Buffer : 2 sub units, 4 fibres each
Number of F/O Pairs4
Core/Clad µm9 /125
Cable Diameter mm (in)4.8 (0.19)
F/O Cable Jacket250 acrylate
F/O Standards (Meets or Exceeds)ITU G 657.A2
Fiber Attenuation≤ 0.4 dB/km at 1310 nm; ≤ 0.25 dB/km at 1550 nm

Testing and Environmental

Storage Temperature °C (°F)-40 to 85 (-40 to 185 )
Operation Temperature °C (°F)-40 to 85 (-40 to 185 )
Installation Temperature °C (°F)-20 to 50 (-4 to 122 )